2.42.2.1 Settings of the Temperature Detection Function

Addr.
Setting Title
9011A
RTD 1 TYPE
9012A
RTD 1 LOCATION
9013
RTD 1 STAGE 1
9014
RTD 1 STAGE 1
9015
RTD 1 STAGE 2
9016
RTD 1 STAGE 2
9021A
RTD 2 TYPE
9022A
RTD 2 LOCATION
9023
RTD 2 STAGE 1
9024
RTD 2 STAGE 1
9025
RTD 2 STAGE 2
9026
RTD 2 STAGE 2
9031A
RTD 3 TYPE
9032A
RTD 3 LOCATION
9033
RTD 3 STAGE 1
9034
RTD 3 STAGE 1
7UM62 Manual
C53000-G1176-C149-3
Setting Options
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
Oil
Ambient
Winding
Bearing
Other
-50..250 °C; ∞
-58..482 °F; ∞
-50..250 °C; ∞
-58..482 °F; ∞
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
Oil
Ambient
Winding
Bearing
Other
-50..250 °C; ∞
-58..482 °F; ∞
-50..250 °C; ∞
-58..482 °F; ∞
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
Oil
Ambient
Winding
Bearing
Other
-50..250 °C; ∞
-58..482 °F; ∞
Temperature Detection by Thermoboxes
Default Setting
Pt 100 Ohm
RTD 1: Type
Winding
RTD 1: Location
100 °C
RTD 1: Temperature Stage 1
Pickup
212 °F
RTD 1: Temperature Stage 1
Pickup
120 °C
RTD 1: Temperature Stage 2
Pickup
248 °F
RTD 1: Temperature Stage 2
Pickup
not connected
RTD 2: Type
Other
RTD 2: Location
100 °C
RTD 2: Temperature Stage 1
Pickup
212 °F
RTD 2: Temperature Stage 1
Pickup
120 °C
RTD 2: Temperature Stage 2
Pickup
248 °F
RTD 2: Temperature Stage 2
Pickup
not connected
RTD 3: Type
Other
RTD 3: Location
100 °C
RTD 3: Temperature Stage 1
Pickup
212 °F
RTD 3: Temperature Stage 1
Pickup