CHAPTER 6: COMMUNICATIONS

Unbuffered report control configuration

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
SPCSO 1 ctlModel
Range: 0, 1, 2
Default: 1
The GGIO5 control configuration settings are used to set the control model for each
input. The available choices are "0" (status only), "1" (direct control), and "2" (SBO with
normal security).
IEC 61850 unbuffered reporting is provided in the GGIO1 logical nodes (for binary status
values), GGIO4 logical nodes (for analog value points), and MMXU1 to MMXU4 (for analog
measured values). Report settings can be configured using the EnerVista UR
Setup software, substation configurator software, or via an IEC 61850 client.
Select the Settings > Communications > IEC 61850 > Unbuffered Report Control
Configuration menu to open the IEC 61850 unbuffered report configuration window.
Figure 111: IEC 61850 unbuffered report control configuration
The following settings are available for each unbuffered report. Up to 18 unbuffered
reports can be configured. Changes to the report configuration take effect when the
Plus
D90
is restarted.
Disconnect any IEC 61850 client connection to the D90
to the unbuffered report configuration. Disconnecting the rear Ethernet connection from
Plus
the D90
disconnects the IEC 61850 client connection.
Unbuffered Reports RptID
Range: up to 65 alphanumeric characters
Default: empty
This setting specifies the name for the IEC 61850 unbuffered report.
Unbuffered Reports OptFlds
Range: 0 to 65535 in steps of 1
Default: 0
This setting specifies a bitmask that selects the option fields. The following bits are
Plus
supported by the D90
Bit 1 — Sequence-number
Bit 2 — Report-time-stamp
Bit 3 — Reason-for-inclusion
Bit 4 — Data-set-name
Bit 5 — Data-reference
Bit 6 — Not supported for unbuffered reports
Bit 7 — Not supported for unbuffered reports
Bit 8 — Conf-revision
:
IEC 61850 COMMUNICATIONS
Plus
Plus
prior to making setting changes
139