Ggio4 Analog Configuration - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

IEC 61850 COMMUNICATIONS

GGIO4 analog configuration

136
Figure 108: IEC 61850 GGIO2 control configuration
The following setting is available for each of the 64 GGIO2 control points. Each control
point is mapped to a corresponding D90
control point SPCSO 3 is mapped to protection virtual input 3.
SPCSO 1 ctlModel
Range: 0, 1, 2
Default: 1
The GGIO2 control configuration settings are used to set the control model for each
input. The available choices are "0" (status only), "1" (direct control), and "2" (SBO with
normal security).
The GGIO4 logical node provides access to as many as 32 analog value points, as well as
associated timestamps and quality flags. The data content must be configured before the
data can be used. GGIO4 provides analog values for access by clients.
It is intended that clients use GGIO4 to access generic analog values from the D90
Settings are used to select the number of analog values available in GGIO4 (4 to 32) as well
as FlexAnalog values that determine the value of the GGIO4 analog inputs. Clients can
utilize polling or the IEC 61850 unbuffered reporting feature available from GGIO4 to obtain
the analog values provided by GGIO4.
Select the Settings > Communications > IEC 61850 > GGIO4 Analog Configuration menu
item to open the GGIO4 analog configuration window.
Plus
protection virtual input. For example, GGIO2
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL