Protection Features - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

PRODUCT DESCRIPTION

Protection features

Distance protection
10
Figure 7: Front panel USB connection
Plus
The D90
is designed for superior performance and ease-of-use, providing a single
platform solution for protecting transmission lines from medium voltage (MV) to extra high
voltage (EHV) and cables of various voltage levels. The scalable platform consists of
protection, control, automation, monitoring, communication, digital fault recorder (DFR)
and security functionality. The incremental scaling allows customization in building the
device to suit specific requirements. The convergent platform integrates multiple devices,
eliminating external devices, and reduces the footprint of relay panels, resulting in reduced
wiring, commissioning, and capital costs.
Plus
The core of the D90
relay is the subcycle distance function providing a high degree of
sensitivity and selectivity for all types of faults. The distance function features five zones of
phase distance and ground distance protection, providing the user the utmost flexibility of
making each zone directional, non directional, or reverse. This allows customization to a
variety of applications, including primary line protection, backup protection for busbars,
and backup protection for generators, transformers, and reactors. The D90
applied to power systems with different earthing conditions, lines with in-zone
transformers or tapped transformer feeders and overhead lines with series compensation.
Each zone element for the phase and ground distance can be set to the quadrilateral or
mho characteristic with the flexibility of designing different characteristic shapes to suit for
different power system conditions.
The advanced comparator based distance elements provide utmost security, sensitivity,
and selectivity for different types of faults. Superior digital filtering techniques provide
secure and optimum reach accuracy even under worst-case CVT transients without
compromising the operating time. Secure direction detection is achieved by using positive
sequence memory voltage polarization providing reliable directionality for worst-case
Plus
close-in faults. The D90
provides fast, secure, and reliable faulted phase identification for single pole tripping and
proper fault distance calculation for a variety of power system conditions. An additional
voltage monitoring function provides extra security to the distance element, which can be
used to block the distance elements under voltage transformer fuse failure conditions.
For additional information, refer to:
Distance elements
on page 187
employs a well-proven algorithm for phase selection, which
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTION
Plus
can be

Advertisement

Table of Contents
loading

Table of Contents