IEC 61850 COMMUNICATIONS
Fixed GOOSE transmission
116
Figure 94: GSSE transmission configuration settings
The following settings are available.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables GSSE transmission.
ID
Range: up to 65 ASCII characters
Default: GSSEOut
This setting represents the IEC 61850 GSSE application ID name string sent as part of
each GSSE message. This name string identifies the GSSE message to the receiving
device.
Destination MAC
Range: standard MAC address format
Default: 00 00 00 00 00 00
This setting specifies the destination Ethernet MAC address for the GSSE transmission.
This address must be a multicast address and the least significant bit of the first byte
must be set.
If this setting is specified as "00 00 00 00 00 00" (the default value), then a multicast MAC
address is formed based on the MAC address of Ethernet ports 2 and 3. The MAC address
of Ethernet port 2 is the MAC address of Ethernet port 1 incremented by 1. The MAC
address of Ethernet port 3 is the MAC address of Ethernet port 1 incremented by 2.
GSSE Minimum Hold Time
Range: 50 to 4000 ms in steps of 1
Default: 400 ms
This setting specifies the minimum hold time for GSSE transmission.
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Transmission > Fixed GOOSE menu to open the fixed GOOSE transmission configuration
window.