GE D90 Plus Instruction Manual page 478

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

AUTOMATION INPUTS AND OUTPUTS
Contact input chatter detection
468
Nominal voltage
48 V
125 V
250 V
Events
Range: Enabled, Disabled
Default: Enabled
If this setting is "Enabled," every change in the contact input state triggers an event in
the event recorder.
Plus
The D90
has a chatter detection feature. When enabled, the IED monitors the number
of state changes that occur within a set duration. If this value exceeds a set value, then a
trouble condition is declared for the input and the
The input trouble alarm impacts relay functionality as follows:
Automation logic operands — Operand state is blocked
DNP 3.0 communications — Reporting of the input is blocked
IEC 60870-5-104 communications — Reporting of the input is blocked
IEC 61850 GSSE and IEC 61850 GOOSE — Reporting of the input is blocked
Sequence of events recorder — Reporting of the input is blocked
The trouble condition resets if the input undergoes no state changes for a duration equal
to twice the chatter time setting.
Figure 397: Chatter detection example
Select the Settings > Automation > Automation Inputs/Outputs > Contact Inputs >
Chatter Detection menu to access the contact input chatter detection settings.
Figure 398: Contact input chatter detection configuration
The following settings are applied to all available protection and automation contact
inputs.
Validation threshold
33.6 V
87.5 V
175 V
CONTACT INPUT TROUBLE
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 8: AUTOMATION
operand asserts.

Advertisement

Table of Contents
loading

Table of Contents