GE D90 Plus Instruction Manual page 477

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 8: AUTOMATION
NOTE:
Contact input settings
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
When the input detects a voltage decrease, the input circuitry draws 10 mA of current. If
the voltage decrease is due to a state change then the voltage quickly decreases,
speeding up the recognition of the reset of the field contact by quickly discharging any
input capacitance.
The contact input update time is 1 ms. However, depending on where the contact input
status change is triggered within a 1 ms window, the worst-case contact input recognition
time is 2 ms.
Select the Settings > Automation > Automation Inputs/Outputs > Contact Inputs >
Contact Inputs menu to access the automation contact input configuration settings.
Figure 396: Automation contact input configuration settings
The contact inputs menu contains configuration settings for each input. Upon startup, the
relay processor determines (from an assessment of the installed modules) which contact
inputs are available and then displays settings for only those inputs. The following settings
are available for each contact input.
ID
Range: up to 12 alphanumeric characters
Default: Cont Ip 1
An alphanumeric identifier can be assigned to a contact input for diagnostic, setting,
and event recording purposes. The "CONTACT IP 1" text in event records and automation
logic operands are replaced by the text programmed in this setting.
Debounce Time
Range: 1.50 to 16.00 ms in steps of 0.25
Default: 2.00 ms
This setting defines the time required for the contact to overcome contact bouncing
conditions. As this time differs for different contact types and manufacturers, program it
as a maximum contact debounce time (per manufacturer specifications) plus additional
margin to ensure proper operation.
Nominal Voltage
Range: 24 to 250 volts in steps of 1
Default: 125 volts
This setting specifies the range required to validate a closed contact input. This range is
fixed at 70 to 130% of this setting value, with an absolute minimum of 20 volts and an
absolute maximum of 285 volts.
Table 29: Nominal voltage setting for typical battery voltages
Nominal voltage
24 V
AUTOMATION INPUTS AND OUTPUTS
Validation threshold
20 V
467

Advertisement

Table of Contents
loading

Table of Contents