GE D90 Plus Instruction Manual page 271

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 7: PROTECTION
Negative-sequence directional overcurrent
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
There are two negative-sequence directional overcurrent protection elements available.
The element provides both forward and reverse fault direction indications through its
output operands
NEG SEQ DIR OC1 FWD
operand is asserted if the magnitude of the operating current is above a pickup level
(overcurrent unit) and the fault direction is seen as forward or reverse, respectively
(directional unit).
The overcurrent unit of the element essentially responds to the magnitude of a
fundamental frequency phasor of either the negative-sequence or neutral current as per
user selection. Do not mistake the zero-sequence current with the neutral current, as there
is a factor of three difference.
A positive-sequence restraint is applied for better performance: a small user-
programmable portion of the positive-sequence current magnitude is subtracted from the
negative or zero-sequence current magnitude, respectively, when forming the element
operating quantity.
The positive-sequence restraint allows for more sensitive settings by counterbalancing
spurious negative-sequence and zero-sequence currents resulting from
System unbalances under heavy load conditions
Transformation errors of current transformers (CTs)
Fault inception and switch-off transients
The positive-sequence restraint must be considered when testing for pickup accuracy and
response time (multiple of pickup). The positive-sequence restraint is removed for low
currents. If the positive-sequence current is less than 0.8 pu, then the restraint is removed
by setting the constant K to zero. This results in better response to high-resistance faults
when the unbalance is very small and there is no danger of excessive CT errors, as the
current is low.
The operating quantity depends on the way the test currents are injected into the D90
For single-phase injection,
I
= ⅓ × (1 – K) × I
for I_2 mode and
op
injected
I
= (1 – K) × I
for I_0 mode if I_1 > 0.8 pu
op
injected
The directional unit uses the negative-sequence current (I_2) and negative-sequence
voltage (V_2).
The following tables define the negative-sequence directional overcurrent element.
Table 16: Negative-sequence directional overcurrent unit
Mode
Negative-sequence
Zero-sequence
Table 17: Negative-sequence directional unit
Mode
Direction
Negative-sequence
Forward
Reverse
Zero-sequence
Forward
Reverse
The negative-sequence voltage must be greater than the Voltage Cutoff Level of the
general voltage inputs (found under the Protection > Power System > AC Inputs - Voltage
settings) to be validated for use as a polarizing signal. If the polarizing signal is not
GROUPED PROTECTION ELEMENTS
and
REV, respectively. The output
NEG SEQ DIR OC1
Operating current
I
= |I_2| – K × |I_1|
op
I
= 3 × (|I_0| – K × |I_1|) if |I_1| > 0.8 pu
op
I
= 3 × |I_0| if |I_1| ≤ 0.8 pu
op
Compared phasors
–V_2 + Z_offset × I_2 and I_2 × 1∠ECA
–V_2 + Z_offset × I_2 and –(I_2 × 1∠ECA)
–V_2 + Z_offset × I_2 and I_2 × 1∠ECA
–V_2 + Z_offset × I_2 and –(I_2 × 1∠ECA)
Eq. 35
Plus
.
261

Advertisement

Table of Contents
loading

Table of Contents