CHAPTER 7: PROTECTION

Contact outputs

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 334: Protection contact input actual values
The following actual values are available for all protection contact inputs.
Name
Range: up to 12 alphanumeric characters
This value displays the programmed
Status
Range: On, Off
This value indicates the logic state of the protection contact input.
Upon startup of the unit, the main processor determines from an assessment of the
modules installed in the chassis which contact outputs are available and presents the
settings for only these outputs.
Select the Settings > Protection > Protection Inputs/Outputs > Contact Outputs menu
to access the contact output configuration settings.
Figure 335: Protection contact output configuration settings
The following settings are available for all contact outputs.
ID
Range: up to 12 alphanumeric characters
Default: Cont Op 1
This setting specifies an alphanumeric identifier for the contact output.
Operate
Range: any FlexLogic operand or shared operand
Default: as shown above
This setting selects an operand (virtual output, element state, contact input, or virtual
input) that operates the contact output when asserted.
PROTECTION INPUTS AND OUTPUTS
for the corresponding protection contact input.
ID
393