CHAPTER 13: SECURITY

EnerVista security management system

Enable the security management system

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Access Authorization Timeout
Range: 5 to 480 minutes in steps of 1
Default: 30 minutes
This setting specifies the timeout delay for setting access. This setting applies when the
Local Setting Authorization
any operand except "ON" or "OFF." The states of any selected operands are continuously
monitored for an off-to-on transition. When this occurs, setting access is permitted and
the timer programmed with this setting value is started. When this timer expires, setting
access is immediately denied. If access is permitted and an off-to-on transition of the
selected operand is detected, the timeout restarts. The status of this timer is updated
every five seconds.
Password Access Events
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the logging of dual-permission security access events
in the event recorder.
IThe EnerVista security management system is a role-based access control (RBAC) system
that allows a security administrator to manage the security privileges of multiple users.
This allows for access control of UR
substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004.
The EnerVista security system allows an administrator to manage access privileges of
multiple users of EnerVista.
It is disabled by default to allow access to the device immediately after installation. When
security is disabled, all users have administrator access. GE recommends enabling the
EnerVista security before placing the device in service.
To enable the security system and require password use:
1.
Select the Security > User Management menu to open the user management
configuration window.
ENERVISTA SECURITY MANAGEMENT SYSTEM
or
Remote Setting Authorization
Plus
-series devices by multiple personnel within a
settings are programmed to
613