GE D90 Plus Instruction Manual page 498

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

AUTOMATION LOGIC
488
Aut VO 2 to 255...........................................The operands listed above are available for the automation
Breaker control operands
BKR CNTRL1 CLOSE CMD .......................Asserted when a close command is issued on breaker 1 from
BKR CNTRL1 INTERLCK BYPS................Asserted when interlocking is bypassed for breaker 1.
BKR CNTRL1 OPEN CMD.........................Asserted when an open command is issued on breaker 1 from
BKR CNTRL2 .................................................The operands listed above are also available for all breakers.
Breaker interlocking operands
BKR INTERLK1 CLS PERM........................Asserted when all conditions have been satisfied for closing
BKR INTERLK1 OPEN PERM....................Asserted when all conditions have been satisfied for opening
BKR INTERLK1 TAGGED ...........................Asserted when a tag is applied to breaker 1.
BKR INTERLK2..............................................The operands listed above are available for all breaker
Automation contact input operands
Cont Ip 1 OFF...............................................Asserted when the field contact connected to contact input 1 is
Cont Ip 1 ON.................................................Asserted when the field contact connected to contact input 1 is
Cont Ip 1 TRB OFF......................................Asserted when there are no problems with contact input 1.
Cont Ip 1 TRB ON........................................Asserted when there is an internal or external problem with
Cont Ip 2 to 40.............................................The operands listed above are available for automation
Automation contact output operands
Cont Op 1 IOff..............................................Asserted when contact output 1 with current monitoring is
Cont Op 1 IOn..............................................Asserted when contact output 1 with current monitoring is
Cont Op 1 VOff ............................................Asserted when contact output 1 with voltage monitoring is
Cont Op 1 VOn.............................................Asserted when contact output 1 with voltage monitoring is
Cont Op 2 to 40 ..........................................The operands listed above are available for automation
Disconnect control operands
DISC CNTRL1 CLOSE CMD......................Asserted when disconnect 1 is closed.
DISC CNTRL1 INTERLCK BYPS...............Asserted when interlocking has been bypassed for disconnect
DISC CNTRL1 LOCAL SELECT ................Asserted when disconnect 1 has been selected from the front
DISC CNTRL1 OPEN CMD........................Asserted when disconnect 1 is open.
DISC CNTRL1 REMOTE SELECT.............Asserted when disconnect 1 has been selected from SCADA.
DISC CNTRL2................................................The operands listed above are available for all disconnects.
virtual outputs 2 through 255. These operands reflect the
programmed names for the automation virtual outputs.
breaker control.
breaker control.
breaker 1.
breaker 1.
interlocking elements.
opened.
closed.
contact input 1.
contact inputs 2 through 40. These operands reflect the
programmed names for the automation contact inputs.
opened.
closed.
opened.
closed.
contract outputs 2 through 40. These operands reflect the
programmed names for the automation contact outputs.
1.
panel HMI.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 8: AUTOMATION