GROUPED PROTECTION ELEMENTS
202
Figure 178: Ground distance settings configuration
The following settings are available for each ground distance zone. There are five ground
distance zones of protection in each setting group.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the phase distance protection feature.
Direction
Range: Forward, Reverse, Non-directional
Default: Forward
All ground distance zones are reversible. The forward direction is defined by the
setting and the reverse direction is shifted by 180° from that angle. The non-directional
zone spans between the forward reach impedance defined by the
settings, and the reverse reach impedance defined by the
settings.
Reach RCA
Shape
Range: Mho, Quad
Default: Mho
This setting selects the shape of the ground distance characteristic between the mho
and quadrilateral characteristics. The selection is available on a per-zone basis.
The figures show the directional and non-directional mho and quadrilateral ground
distance characteristics.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: PROTECTION
RCA
Reach
and
RCA
and
Reverse Reach
Reverse