GE D90 Plus Instruction Manual page 136

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

IEC 61850 COMMUNICATIONS
Remote outputs: UserSt bit pairs
126
Figure 101: Remote outputs DNA bit pair configuration settings
The following settings are available for each of the 32 remote outputs.
Operand
Range: any automation logic or FlexLogic operand
Default: Off
This setting specifies the FlexLogic operand assigned to DNA point 1.
Events
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the logging of remote output DNA bit pair events in the
sequence of events recorder.
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote
devices. Each digital point in the message must be programmed to carry the state of a
specific FlexLogic operand. This operand setting is used to select the operand that
represents a specific UserSt function (as selected by the user) to be transmitted.
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Inputs/Outputs > Remote Outputs UserSt menu to open the remote inputs configuration
window.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: COMMUNICATIONS

Advertisement

Table of Contents
loading

Table of Contents