CHAPTER 5: ENERVISTA SOFTWARE
Online device traceability information
Additional traceability rules
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 68: Settings file report showing traceability data
Plus
The D90
serial number and file transfer date are available for an online device through
the actual values. Select the Actual Values > Product Information > Model Information
menu item within the EnerVista online window as shown in the example.
Figure 69: Traceability data in Actual Values window
The following additional rules apply for the traceability feature:
•
If the user changes any settings within the settings file in the offline window, then the
traceability information is removed from the settings file
•
If the user creates a new settings file, then no traceability information is included in
the settings file
•
If the user converts an existing settings file to another revision, then any existing
traceability information is removed from the settings file
•
If the user duplicates an existing settings file, then any traceability information is
transferred to the duplicate settings file
SETTINGS FILE TRACEABILITY
89