CHAPTER 5: ENERVISTA SOFTWARE

Online device traceability information

Additional traceability rules

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 68: Settings file report showing traceability data
Plus
The D90
serial number and file transfer date are available for an online device through
the actual values. Select the Actual Values > Product Information > Model Information
menu item within the EnerVista online window as shown in the example.
Figure 69: Traceability data in Actual Values window
The following additional rules apply for the traceability feature:
If the user changes any settings within the settings file in the offline window, then the
traceability information is removed from the settings file
If the user creates a new settings file, then no traceability information is included in
the settings file
If the user converts an existing settings file to another revision, then any existing
traceability information is removed from the settings file
If the user duplicates an existing settings file, then any traceability information is
transferred to the duplicate settings file