Iec 60870-5-104 Communications; Iec 60870-5-104 Protocol - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

IEC 60870-5-104 COMMUNICATIONS

IEC 60870-5-104 communications

IEC 60870-5-104 protocol

112
Figure 90: DNP user point list configuration settings
The following settings are available for points 0 through 255.
DNP Binary Input Point 0, DNP Binary Input Point 1,..., DNP Binary Input Point 255
Range: any FlexLogic operand
Default: Off
These settings represent DNP binary input points and are configured by assigning an
appropriate FlexLogic operand to each. Up to 256 binary input points can be configured
for the DNP protocol. Changes take effect when the D90
DNP Analog Input Point 0, DNP Analog Input Point 2,..., DNP Analog Input Point 255
Range: any FlexAnalog parameter
Default: Off
These settings represent DNP analog input points and are configured by assigning an
appropriate FlexAnalog parameter to each. Up to 256 analog input points can be
configured for the DNP protocol. Changes take effect when the D90
The IEC 60870-5-104 server can support two clients simultaneously. It can report any
indication or measurement and operate any output present in the device. These point lists
are shared with the DNP protocol.
Select the Settings > Communications > IEC 60870-5-104 > Protocol menu to open the
IEC 60870-5-104 protocol configuration window.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: COMMUNICATIONS
Plus
is restarted.
Plus
is restarted.