CONTROL ELEMENTS
Terminal one-pole open
352
Figure 297: Terminal three-pole open logic
The autoreclose scheme also has dedicated logic to determine if one pole is opened at the
local terminal. For single-breaker operation, the
operand is used to derive this signal. For the 1&2 sequence, both breakers must
OPEN
either declare one pole open or be open or out-of-service. For the 1-2 sequence, breaker 1
must declare one pole open and breaker 2 must declare one pole open or be open or out-
of-service. For the 2-1 sequence, breaker 2 must declare one pole open and breaker 1
must declare one pole open or be open or out-of-service. Alternately, a user-defined
setting is available to generate this signal.
BREAKER 1 ONE P OPEN
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: PROTECTION
or
BREAKER 2 ONE P