GE D90 Plus Instruction Manual page 187

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 7: PROTECTION
NOTE:
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Phase VT Secondary
Range: 50.0 to 240.0 volts in steps of 0.1
Default: 66.4 volts
This setting specifies the nominal phase VT voltage for the corresponding voltage input.
It is used typically to derive secondary voltage values from the per-unit settings used in
protection elements.
The typical
Phase VT Secondary
appearing at the relay input terminals when nominal voltage is applied to the VT
primary. For example, on a system with a 13.8 kV nominal primary voltage and with a
14400:120 V VT in a delta connection, the secondary voltage is (13800 V / 14400) × 120 =
115 V. Thus, the
Phase VT Secondary
Phase VT Ratio
Range: 1.00 to 24000.00 in steps of 0.01
Default: 1.00
This setting specifies the phase VT ratio for the corresponding voltage input. It is used
typically for calculation of primary metering values or matching primary voltage in a
synchrocheck application.
Auxiliary VT Connection
Range: Vag, Vbg, Vcg, Vab, Vbc, Vca, Vn
Default: Vag
This setting specifies the auxiliary VT connection type for the corresponding voltage
input.
Auxiliary VT Secondary
Range: 50.0 to 240.0 volts in steps of 0.1
Default: 66.4 volts
This setting specifies the nominal auxiliary VT voltage for the corresponding voltage
input. It is used typically to derive secondary voltage values from the per-unit settings
used in protection elements.
Auxiliary VT Ratio
Range: 1.00 to 2400.00 in steps of 0.001
Default:
This setting specifies the auxiliary VT ratio for the corresponding voltage input. It is used
typically for calculation of primary metering values or matching primary voltage in a
synchrocheck application.
Voltage Cutoff Level
Range: 0.1 to 1.0 volts secondary in steps of 0.1
Default: 1.0 volts secondary
This setting specifies the voltage cut-off threshold. Very low secondary voltage
measurements (at the fractional volt level) can be affected by noise. Some users prefer
these low voltages to display as zero, while others prefer the voltage to display even
when the value reflects noise rather than the actual signal. The D90
value to the magnitudes and angles of the measured voltages. If the magnitude is below
the cut-off level, it is substituted with zero. This operation applies to phase voltages,
auxiliary voltages, and symmetrical components. The cut-off operation applies to
quantities used for metering, protection, and control, as well as those used by
communications protocols. Raw samples of the voltages available via oscillography are
not subject cut-off.
Lower the
Voltage Cutoff Level
as valid measurements. Unless dictated otherwise by a specific application, the default
setting of "1.0 V" is recommended.
setting is the phase-to-phase secondary voltage
setting is 115 volts.
setting with care because the D90
POWER SYSTEM
Plus
applies a cut-off
Plus
accepts lower signals
177

Advertisement

Table of Contents
loading

Table of Contents