GE D90 Plus Instruction Manual page 269

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 7: PROTECTION
Negative-sequence instantaneous overcurrent
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 221: Negative-sequence time overcurrent scheme logic
The negative-sequence instantaneous overcurrent element can be used as an
instantaneous function with no intentional delay or as a definite time function. The
element responds to the negative-sequence current fundamental frequency phasor
magnitude (calculated from the phase currents) and applies a positive-sequence restraint
for better performance: a small portion (12.5%) of the positive-sequence current
magnitude is subtracted from the negative-sequence current magnitude when forming
the operating quantity.
The positive-sequence restraint allows for more sensitive settings by counterbalancing
spurious negative-sequence currents resulting from
System unbalances under heavy load conditions
Transformation errors of current transformers (CTs) during three-phase faults
Fault inception and switch-off transients during three-phase faults
The positive-sequence restraint must be considered when testing for pickup accuracy and
response time (multiple of pickup). The operating quantity depends on how the test
currents are injected into the relay. The operating quantity for single-phase injection is
The operating quantity for three-phase injection, opposite rotation, is
Select the Settings > Protection > Elements > Group 1 > Current > Negative Sequence
IOC menu to open the negative-sequence instantaneous overcurrent configuration
window.
Figure 222: Negative-sequence instantaneous overcurrent configuration settings
The following settings are available for each negative-sequence instantaneous
overcurrent element.
GROUPED PROTECTION ELEMENTS
Eq. 32
Eq. 33
Eq. 34
259

Advertisement

Table of Contents
loading

Table of Contents