The following settings are available for each dataset for configurable GOOSE transmission.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables configurable GOOSE transmission.
ID
Range: up to 65 ASCII characters
Default: GOOSEOut_1
This setting represents the IEC 61850 GOOSE application ID (GoID) name string sent as
part of each GOOSE message. This name string identifies the GOOSE message to the
receiving device.
Destination MAC
Range: standard MAC address format
Default: 00 00 00 00 00 00
This setting specifies the destination Ethernet MAC address for the configurable GOOSE
transmission. This address must be a multicast address and the least significant bit of
the first byte must be set.
If this setting is specified as "00 00 00 00 00 00" (the default value), then a multicast MAC
address is formed based on the MAC address of Ethernet ports 2 and 3. The MAC address
of Ethernet port 2 is the MAC address of Ethernet port 1 incremented by 1. The MAC
address of Ethernet port 3 is the MAC address of Ethernet port 1 incremented by 2.
VLAN Priority
Range: 0 to 7 in steps of 1
Default: 4
This setting indicates the Ethernet priority of GOOSE messages. This allows GOOSE
messages to have higher priority than other Ethernet data. This setting is required by IEC
61850.
VLAN ID
Range: 0 to 4096 in steps of 1
Default: 0
This setting allows the selection of a specific VLAN ID for each GOOSE sending device.
This value can be left at its default if the feature is not required.
ETYPE APPID
Range: 0 to 16383 in steps of 1
Default: 0
This setting allows the selection of a specific application ID for each GOOSE sending
device. This value can be left at its default if the feature is not required. This setting is
required by IEC 61850.
ConfRev
Range: 1 to 16383 in steps of 1
Default: 1
This value changes automatically as described in IEC 61850 part 7-2.
Minimum Time to Live
Range: 50 to 4000 ms in steps of 1
Default: 400 ms
This setting specifies the minimum time to live for the GOOSE transmission data set.