Install Software; System Requirements - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 3: INSTALLATION

Install software

System requirements

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Plus
The UR
-series C37.94 communication module can be connected to the electrical
interface (G.703, RS422, or X.21) of a non-compliant digital multiplexer via an optical-to-
electrical interface converter that supports the IEEE C37.94 standard. The following figure
shows the concept.
Figure 37: IEEE C37.94 connection to non-compliant digital multiplexer
The
Protocol Encoding
setting is used to set the protocol and clock option for the IEEE
C37.94 protocol selection. If the setting is programmed as "C37.94 Internal Clock", then the
system clock is generated internally. For an external or loop timing scheme, the system
clock is derived from the received line signal. For these cases, the program the setting to
"C37.94 External Clock" or "Default" for connection to higher-order systems.
Plus
The UR
-series direct fiber module can be connected directly to another UR
UR-series device with an installed direct fiber module.
Figure 38: Direct fiber to direct fiber connection
Plus
The EnerVista UR
Setup software provides tools to monitor the status of your protected
asset, maintain the device, and integrate information measured by the D90
SCADA monitoring systems. Convenient COMTRADE and sequence of events viewers are
an integral part of the software included with every D90
out post-mortem event analysis to ensure proper protection system operation.
The relay front panel EnerVista UR
Plus
the D90
. The software is the preferred method to edit settings and view actual values
because the computer monitor can display more information.
The minimum system requirements for the EnerVista software are as follows:
Pentium class or higher processor (Pentium II 300 MHz or higher recommended)
Windows XP, Vista, 7 (64-bit), or Server 2008 (64-bit)
Internet Explorer 4.0 or higher
128 MB of RAM (256 MB recommended)
200 MB of available space on system drive and 200 MB of available space on
installation drive
800 × 600 display or higher in high-color mode (16-bit color)
Plus
. This allows the user to carry
Plus
Setup software can be used to communicate with
INSTALL SOFTWARE
Plus
-series or
Plus
into DCS or
59

Advertisement

Table of Contents
loading

Table of Contents