CHAPTER 7: PROTECTION
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 262: Directional comparison unblocking scheme configuration settings
The following settings are available.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the directional comparison unblocking scheme.
Block
Range: any FlexLogic operand
Default: OFF
This setting allows the user to assign any FlexLogic operand to block the directional
comparison unblocking scheme. Contact inputs from a pilot cut-out switch are typically
used for this purpose.
Permissive Echo
Range: Disabled, Enabled, Custom
Default: Disabled
Enabling this setting sends a permissive echo signal to the remote ends under certain
conditions (see the logic diagram). If set to "Custom," the echo signal is sent if a condition
selected with the
Echo Condition
the echo logic locks out for the time specified by the
of the echo pulse is programmable by the
only if no overreaching and reverse protection elements operate.
Echo Condition
Range: any FlexLogic operand
Default: OFF
This setting specifies and applies an echo condition when the
"Custom."
setting is satisfied. The echo is sent only once and then
Echo Lockout
Echo Duration
setting. The echo is returned
CONTROL ELEMENTS
setting. The duration
setting is
Permissive Echo
311