Type 8792, 8793
Type 8792, 8793
Start-up, operation
position controller Type 8792
procedure:
calibr. POS..Calibrating.the.actual.value.display.POS.(0.–.100%):
→
In the
CAL. USER menu press the arrow keys to select the calibr. POS and confirm with the selection key on
the right (ENTER).
Accept the minimum position:
→
Press the arrow keys to mark the
(SELEC).
→
Approach the minimum position of the valve using the arrow keys (OPN/CLS) and confirm this value by pressing
the selection key on the right (OK).
Accept the maximum position:
→
Press the arrow keys to mark the
(SELEC).
→
Approach the maximum position of the valve using the arrow keys (OPN/CLS) and confirm this value by pressing
the selection key on the right (OK).
calibr. INP.. Calibrating.the.position.set-point.value.(4.–.20.mA;.0.–.20.mA;.0.–.5.V;.0.–.10.V):
→
CAL. USER menu press the arrow keys to select the calibr. INP and confirm with the selection key on
In the
the right (ENTER).
Accept the minimum input signal (0 mA; 4 mA; 0 V):
→
Using the arrow keys, select the
right (INPUT).
→
Specify the minimum value of the unit signal at the input and confirm this value with the selection key on the
right (OK).
Accept the maximum input signal (20 mA; 5 V; 10 V):
→
Using the arrow keys, select the
right (INPUT).
→
Specify the maximum value of the unit signal at the input and confirm this value with the selection key on the
right (OK).
→
USER.. resetting.the.settings.under.CAl.uSEr.to.the.factory.settings:.
copy FACT
→
In the
CAL.USER menu select the copy FACT→USER menu option using the arrow keys and confirm with the
selection key on the right (ENTER).
→
Hold down the selection key on the right (RUN) (for approx. 3 seconds) until the countdown has elapsed.
POS lower X menu option and confirm with the selection key on the right
POS upper X menu option and confirm with the selection key on the right
INP (0 mA; 4 mA; 0 V) menu option and confirm with the selection key on the
INP (20 mA; 5 V; 10 V) menu option and confirm with the selection key on the
english
117