19.5. specifying the standard settings
When starting up the positioner for the first time, implement the following standard settings:
Specify the selected unit signal input for the set-point value default (
(4 – 20 mA; 0 – 20 mA; 0 – 10 V or 0 – 5 V).
Start automatic adjustment of the position controller to the particular operating conditions (
The exact description of the INPUT and X.TUNE functions can be found in the chapter entitled
19.6.Description of the basic functions in the main menu.
The basic settings for the positioner are implemented at the factory. During start-up, however, it is
essential to input the unit signal (INPUT) and run X.TUNE. Using the X.TUNE function, the positioner
automatically determines the optimum settings for the current operating conditions.
If the auxiliary function X.CONTROL is in the main menu while X.TUNE is running, the position controller
dead band DBND is also determined automatically depending on the friction behaviour of the actuator
drive (see chapter entitled 21.3.10.X.CONTROL
INPUT)
Parameterization of the position controller).