Burkert 8792 Operating Instructions Manual page 112

Electropneumatic positioner
Table of Contents

Advertisement

OUT ANALOG -.Configuring.the.analogue.output
Only for the versions:
one analogue output
one analogue and two binary outputs
The feedback signal of the current position (POS) or of the set-point value (CMD) can be transmitted to the control
centre via the analogue output.
OUT ANALOG
Fig. 62:
Operating structure OUTPUT-ANALOG; position controller type Type 8792
Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.
OUT BIN1 -.Configuring.the.binary.output.1
OUT BIN2 -.Configuring.the.binary.output.2
The following description is valid for both binary outputs OUT BIN 1 and OUT BIN 2, as the operation in the menu
is identical.
The binary outputs 1 and 2 can be used for one of the following outputs:
Alarm output for excessively large control deviations of the position controller
for the output of the current position with respect to a specified limit position (> or <)
for the output: actuator in safety position
for the output: sensor break
for the output: operating state (AUTOMATIC / MANUAL)
112
ENTER
OUT POS
OUT CMD
EXIT
OUT type
english
SELEC
Output of the current position
Output of the set-point value
ENTER
4 – 20 mA
0 – 20 mA
0 – 10 V
EXIT
0 – 5 V
Type 8792, 8793
Type 8792, 8793
Start-up, operation
position controller Type 8792
SELEC
Selection of the
unit signal