Burkert 8792 Operating Instructions Manual page 113

Electropneumatic positioner
Table of Contents

Advertisement

Type 8792, 8793
Type 8792, 8793
Start-up, operation
position controller Type 8792
ENTER
OUT BIN 1
OUT BIN 2
EXIT
* If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.
** The permitted control deviation Lim DEV.X XX must not be less than the dead band.
Fig. 63:
Operating structure OUTPUT-BIN1/BIN2; position controller type Type 8792
Normally closed output, in switched state low (≅ 0 V)
Normally opened output, in switched state high (≅ 24 V)
Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.
SELEC
OUT DEV.X
OUT POS
OUT Safepos
OUT ERRSP/CMD
OUT remote
INPUT
Lim. DEV.X 1.0%
*
OK
INPUT
Lim. POS 0%
*
OK
ENTER
OUT BIN 1 type
OUT BIN 2 type
EXIT
Selection: Alarm output for excessively large
control deviation of the position controller
Output: current position with respect to a
specified limit position
Output: actuator in safety position
Output: sensor break
Output: operating state MANUAL / AUTOMATIC
+
Input the limit value for the
Lim. DEV.X: 1.0
permitted control deviation
-
Adjustment range: 1 – 50%**
+
Input the limit position
Lim. POS:
0
-
Adjustment range: 0 – 100%
normally open
normally closed
english
SELEC
Selection of
switching signal
113