16.2. Connection Of The Position Controller Type 8792; Input Signals Of The Control Centre (E.g. Plc) - M12, 8-Pole Plug; Output Signals To The Control Centre (E.g. Plc) - M 12, 8-Pole Plug (Required For Analogue Output Option Only) - Burkert 8792 Operating Instructions Manual

Electropneumatic positioner
Table of Contents

Advertisement

16.2. connection of the position controller Type 8792
16.2.1.
input signals of the control centre (e.g. plc) -
M12, 8-pole plug
Pin Wire.colour* Configuration
1
white
2
brown
5
grey
6
pink
* The indicated wire colours refer to the connection cable, part no. 919061, available as an accessory.
Table 16:
Pin assignment; input signals of the control centre - M12, 8-pole plug
16.2.2.
Output signals to the control centre (e.g. plc) -
M 12, 8-pole plug
(required for analogue output option only)
Connect pins according to the model (options) of the positioner.
Pin
Wire.colour* Configuration
8
red
7
blue
* The indicated wire colours refer to the connection cable, part no. 919061, available as an accessory.
Table 17:
Pin assignment; output signals to the control centre - M12, 8-pole plug
62
Set-point value + (0/4 – 20 mA
or 0 – 5/10 V
Set-point value GND
Binary input
Binary input GND
Analogue feedback +
Analogue feedback GND
english
Type 8792, 8793
Installation
External.circuit./.Signal.level
1
+ (0/4 – 20 mA or 0 – 5 / 10 V)
completely galvanically isolated
2
GND
+
5
6
GND
External.circuit./.signal.level
8
+ (0/4 – 20 mA or 0 – 5 / 10 V)
completely galvanically isolated
7
GND
0 – 5 V
(log. 0)
10 – 30 V (log. 1)

Hide quick links: