Maintenance; Maintenance; Error.messages.and.malfunctions; 39.1. Error Messages On The Display - Burkert 8792 Operating Instructions Manual

Electropneumatic positioner
Table of Contents

Advertisement

38.

MainTenance

The.positioner.Type.8793.is.maintenance-free.when.operated.according.to.the.instructions.in.this.manual.
39.
errOr Messages and MalfuncTiOns
39.1. error Messages on the display
39.1.1.
general error Messages
Display
min
max
CMD error
SP error
PV error
PT100 error
invalid code
EEPROM fault
MFI fault *
* field bus only
Table 52:
General error message, process controller Type 8793
198
Causes.of.error
Minimum input value has been reached Do not reduce value further
Maximum input value has been reached Do not increase value further
Signal error
Set-point value position controller
Signal error
Set-point value process controller
Signal error
Actual value process controller
Signal error
Actual value Pt-100
Incorrect access code
EEPROM defective
Field bus board defective
english
Type 8792, 8793
Servicing and Troubleshooting the
Process Controller Type 8793
remedial.action
Check signal
Check signal
Check signal
Check signal
Input correct access code
Not possible, device defective