Burkert 8792 Operating Instructions Manual page 114

Electropneumatic positioner
Table of Contents

Advertisement

OUT DEV.X..Alarm.output.for.excessively.large.control.deviation.of.the.position.controller:
Press the arrow keys to mark the
(SELEC).
Press the arrow keys to input the
option and accept with the selection key on the right (OK).
The permitted control deviation Lim. DEV.X XX must not be less than the dead band.
In the
OUT BIN1/2 type menu option input the required switching status (normally open / normally closed)
(see Table 32:).
OUT POS . Output.of.the.current.position.with.respect.to.a.specified.limit.position:
Press the arrow keys to mark the
(SELEC).
Press the arrow keys to input the
the selection key on the right (OK).
In the
OUT BIN1/2 type menu option input the required switching status (normally open / normally closed)
(see Table 32:).
OUT BIN1/2
POS > LIM
POS < LIM
* Normally open- output, in switched state high (≅ 24 V)
** Normally closed- output, in switched state low (≅ 0 V)
Table 32: Switching status OUT BIN - POS > LIM; position controller type Type 8792
114
OUT DEV.X menu option and confirm with the selection key on the right
the limit value for the permitted control deviation in the Lim. DEV.X menu
OUT POS menu option and confirm with the selection key on the right
value of the limit position in the Lim. POS 0% menu option and accept with
normally open*
0 V
24 V
english
Type 8792, 8793
Type 8792, 8793
Start-up, operation
position controller Type 8792
normally closed**
24 V
0 V