2.8.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding second-
ary nominal current of the current transformer.
Addr.
Parameter
2401
FCT HS/SOTF-O/C
2404
I>>>
2405A
I>>>>
2406
CBaux for I>>>
2.8.4

Information List

No.
Information
4253
>BLOCK SOTF-O/C
4271
SOTF-O/C OFF
4272
SOTF-O/C BLOCK
4273
SOTF-O/C ACTIVE
4281
SOTF-O/C PICKUP
4282
SOF O/CpickupL1
4283
SOF O/CpickupL2
4284
SOF O/CpickupL3
4285
I>>>>O/C p.upL1
4286
I>>>>O/C p.upL2
4287
I>>>>O/C p.upL3
4289
HS/SOF TRIP1pL1
4290
HS/SOF TRIP1pL2
4291
HS/SOF TRIP1pL3
4292
HS/SOF TRIP 1p
4293
HS/SOF Gen.TRIP
4294
HS/SOF TRIP 3p
4295
HS/SOF TRIPL123
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
2.8 Instantaneous High-Current Switch-onto-Fault Protection (SOTF)
C
Setting Options
ON
OFF
1A
0.10 .. 15.00 A; ∞
5A
0.50 .. 75.00 A; ∞
1A
1.00 .. 25.00 A; ∞
5A
5.00 .. 125.00 A; ∞
local only
local and rem.
Type of In-
formation
SP
>BLOCK Instantaneous SOTF Overcurrent
OUT
SOTF-O/C is switched OFF
OUT
SOTF-O/C is BLOCKED
OUT
SOTF-O/C is ACTIVE
OUT
SOTF-O/C PICKED UP
OUT
SOTF-O/C Pickup L1
OUT
SOTF-O/C Pickup L2
OUT
SOTF-O/C Pickup L3
OUT
High Speed-O/C Pickup I>>>> L1
OUT
High Speed-O/C Pickup I>>>> L2
OUT
High Speed-O/C Pickup I>>>> L3
OUT
High Speed/SOTF-O/C TRIP - Only L1
OUT
High Speed/SOTF-O/C TRIP - Only L2
OUT
High Speed/SOTF-O/C TRIP - Only L3
OUT
High Speed/SOTF-O/C TRIP 1pole
OUT
High Speed/SOTF-O/C General TRIP
OUT
High Speed/SOTF-O/C TRIP 3pole
OUT
High Speed/SOTF-O/C TRIP command L123
Default Setting
ON
Inst. High Speed/SOTF-
O/C is
1.50 A
I>>> Pickup
7.50 A
∞ A
I>>>> Pickup
∞ A
local and rem.
CB-aux check for activa-
tion of I>>>
Comments
Functions
Comments