Appendix
A.7 Settings
Addr.
Parameter
610
FltDisp.LED/LCD
625A
T MIN LED HOLD
640
Start image DD
1103
FullScaleVolt.
1104
FullScaleCurr.
1105
Line Angle
1106
OPERATION POWER
1107
P,Q sign
1111
x'
1111
x'
1112
c'
1112
c'
1113
Line Length
1113
Line Length
1130A
PoleOpenCurrent
1131A
PoleOpenVoltage
1132A
SI Time all Cl.
1133A
T DELAY SOTF
1134
Line Closure
1135
Reset Trip CMD
1136
OpenPoleDetect.
1150A
SI Time Man.Cl
1151
SYN.MAN.CL
1152
Man.Clos. Imp.
1155
3pole coupling
1156A
Trip2phFlt
1161
VECTOR GROUP U
1162
VECTOR GROUP I
1163
TRANS STP IS
1201
STATE OF DIFF.
388
Function
C
Device
Target on PU
Target on TRIP
Device
0 .. 60 min; ∞
Device
image 1
image 2
image 3
image 4
image 5
image 6
P.System Data 2
0.4 .. 1200.0 kV
P.System Data 2
10 .. 10000 A
P.System Data 2
10 .. 89 °
P.System Data 2
0.2 .. 5000.0 MVA
P.System Data 2
not reversed
reversed
P.System Data 2
1A
0.0050 .. 9.5000 Ω/km
5A
0.0010 .. 1.9000 Ω/km
P.System Data 2
1A
0.0050 .. 15.0000 Ω/mi
5A
0.0010 .. 3.0000 Ω/mi
P.System Data 2
1A
0.000 .. 100.000 µF/km
5A
0.000 .. 500.000 µF/km
P.System Data 2
1A
0.000 .. 160.000 µF/mi
5A
0.000 .. 800.000 µF/mi
P.System Data 2
0.1 .. 1000.0 km
P.System Data 2
0.1 .. 650.0 Miles
P.System Data 2
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
P.System Data 2
2 .. 70 V
P.System Data 2
0.01 .. 30.00 sec
P.System Data 2
0.05 .. 30.00 sec
P.System Data 2
only with ManCl
I OR U or ManCl
CB OR I or M/C
I or Man.Close
P.System Data 2
CurrentOpenPole
Current AND CB
Pickup Reset
P.System Data 2
OFF
Current AND CB
w/ measurement
P.System Data 2
0.01 .. 30.00 sec
P.System Data 2
w/o Sync-check
NO
P.System Data 2
(Setting options depend
on configuration)
P.System Data 2
with PICKUP
with TRIP
P.System Data 2
3pole
1pole leading Ø
1pole lagging Ø
P.System Data 2
0 .. 11
P.System Data 2
0 .. 11
P.System Data 2
Solid Earthed
Not Earthed
Diff. Prot
OFF
ON
Setting Options
Default Setting
Target on PU
0 min
image 1
400.0 kV
1000 A
85 °
692.8 MVA
not reversed
0.1500 Ω/km
0.0300 Ω/km
0.2420 Ω/mi
0.0484 Ω/mi
0.010 µF/km
0.050 µF/km
0.016 µF/mi
0.080 µF/mi
100.0 km
62.1 Miles
0.10 A
0.50 A
30 V
0.10 sec
0.25 sec
I or Man.Close
CurrentOpenPole
w/ measurement
0.30 sec
NO
None
with TRIP
3pole
0
0
Solid Earthed
ON
C53000-G1176-C145-6, Release date 02.2011
Comments
Fault Display on LED / LCD
Minimum hold time of lachted
LEDs
Start image Default Display
Measurement: Full Scale Voltage
(100%)
Measurement: Full Scale Current
(100%)
Line Angle
Operational power of protection
zone
P,Q operational measured values
sign
x' - Line Reactance per length
unit
x' - Line Reactance per length
unit
c' - capacit. per unit line len.
µF/km
c' - capacit. per unit line len.
µF/mile
Line Length
Line Length
Pole Open Current Threshold
Pole Open Voltage Threshold
Seal-in Time after ALL closures
minimal time for line open before
SOTF
Recognition of Line Closures
with
RESET of Trip Command
open pole detector
Seal-in Time after MANUAL clo-
sures
Manual CLOSE COMMAND
generation
MANUAL Closure Impulse after
CONTROL
3 pole coupling
Trip type with 2phase faults
Vector group numeral for voltage
Vector group numeral for current
Transformer starpoint is
State of differential protection
SIPROTEC, 7SD610, Manual