Technical Data
4.1 General
4.1.3
Binary Inputs and Outputs
Binary inputs
Number
Rated Voltage Range
Pick-up threshold
- For nominal voltages
- For nominal voltages
- For nominal voltages
Current consumption, energized
Maximum Permissible Voltage
Impulse filter on input
324
7 (configurable)
DC 24 V to 250 V, in 3 ranges, bipolar
Changeable via jumpers
DC 24 V/48 V and
DC 60 V/110 V/125 V
DC 110 V/125 V/220 V/250 V
DC 220 V/250 V
Approx. 1.8 mA
Independent of the control voltage
DC 300 V
220 nF coupling capacitance at 220 V with recovery time > 60 ms
U
≥ DC 19 V
high
U
≤ DC 10 V
low
U
≥ DC 88 V
high
U
≤ DC 44 V
low
U
≥ DC 176 V
high
U
≤ DC 88 V
low
SIPROTEC, 7SD610, Manual