Deployment Conditions; Constructive Versions - Siemens SIPROTEC 7SD610 Manual

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

4.1.8

Deployment Conditions

The protection device is designed for installation in normal relay rooms and plants, so that electromagnetic immunity is
ensured if installation is done properly.
In addition the following is recommended:
• Contacts and relays operating within the same cabinet or on the same relay board with digital protection equipment,
should be in principle provided with suitable surge suppression components.
• For substations with operating voltages of 100 kV and above, all external cables shall be shielded with a conductive
shield earthed at both ends. For substations with lower operating voltages, no special measures are normally required.
• For substations with lower operating voltages, no special measures are normally required. When removed, many com-
ponents are electrostatically endangered; when handling the EEC standards (standards for Electrostatically Endan-
gered Components) must be observed. The modules, boards, and device are not endangered when the device is com-
pletely assembled.
4.1.9

Constructive versions

Housing
Dimensions
in flush mounting housing
In panel surface mounting housing
Degree of protection according to IEC 60529
For surface mounting housing equipment
For the device in flush-mounted housing
Front
Rear
for personell protection
UL-certification conditions
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
Housing
7XP20
See dimensional drawings, Section 4.17
(for maximum number of components)
5 kg (11.02 lb)
9.5 kg (20.94 lb)
IP 51
IP 51
IP 50
IP 2x with closed protection cover
Type 1 for front panel mounting
Surrounding air temperature:
o
tsurr: max. 70
C or 158 °F, normal operation
Technical Data
4.1 General
Weight
333