Functions
2.13 Circuit Breaker Failure Protection
Delay times
When the initiatiation conditions are fulfilled, the associated timers are started. The circuit breaker pole(s) must
open before the associated time has elapsed.
Different delay times are possible for 1-pole and 3-pole initiation. An additional delay time can be used for two-
stage circuit breaker failure protection.
With single-stage circuit breaker failure protection, the trip command is relayed to the adjacent circuit breakers
which interrupt the fault current if the local feeder breaker fails (see Figure 2-64 and Figure 2-65). The adjacent
circuit breakers are those located at the busbar or busbar section to which the feeder under consideration is
connected. The possible initiation conditions for the circuit breaker failure protection are those discussed
above. Depending on the application of the feeder protection, common phase or phase-segregated initiation
conditions may occur. The circuit breaker failure protection always trips 3-pole.
The simplest solution is to start the delay timer T2 (Figure 2-73). The phase-segregated initiation signals are
omitted if the feeder protection always trips 3-pole or if the circuit breaker is not capable of 1-pole tripping.
If different delay times are required after a 1-pole trip or 3-pole trip it is possible to use the timer stages T1-
1pole and T1-3pole according to Figure 2-74.
Figure 2-73
Figure 2-74
With two-stage circuit breaker failure protection the trip command of the feeder protection is usually repeated,
after a first time stage, to the feeder circuit breaker, often via a second trip coil or set of trip coils, if the circuit
breaker has not responded to the original trip command. A second time stage monitors the response to this
repeated trip command and trips the circuit breakers of the relevant busbar section if the fault has not yet been
cleared after this second time.
For the first stage, a different delay T1-1pole can be set for 1-pole trip than for 3-pole trip by the feeder pro-
tection. Additionally, you can select (by setting parameter 1p-RETRIP (T1)) whether this repeated trip should
be 1-pole or 3-pole. In case of a multi-pole tripping of the feeder protection, T1-1pole and T1-3pole are
started simultaneously. By means of T1-3pole, the tripping of the circuit breaker failure protection can be ac-
celerated in comparison to T1-1pole.