Siemens SIPROTEC 7SD610 Manual page 394

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

Appendix
A.7 Settings
Addr.
Parameter
3621
O/U FREQ. f3
3622
f3 PICKUP
3623
f3 PICKUP
3624
T f3
3631
O/U FREQ. f4
3632
f4 PICKUP
3633
f4 PICKUP
3634
T f4
3701
Uph-e>(>)
3702
Uph-e>
3703
T Uph-e>
3704
Uph-e>>
3705
T Uph-e>>
3709A
Uph-e>(>) RESET
3711
Uph-ph>(>)
3712
Uph-ph>
3713
T Uph-ph>
3714
Uph-ph>>
3715
T Uph-ph>>
3719A
Uphph>(>) RESET
3721
3U0>(>) (or Ux)
3722
3U0>
3723
T 3U0>
3724
3U0>>
3725
T 3U0>>
3728A
3U0>(>) Stabil.
3729A
3U0>(>) RESET
3731
U1>(>)
3732
U1>
3733
T U1>
3734
U1>>
3735
T U1>>
3736
U1> Compound
3737
U1>> Compound
3739A
U1>(>) RESET
3741
U2>(>)
3742
U2>
3743
T U2>
3744
U2>>
3745
T U2>>
394
Function
C
Frequency Prot.
ON: Alarm only
ON: with Trip
OFF
Frequency Prot.
45.50 .. 54.50 Hz
Frequency Prot.
55.50 .. 64.50 Hz
Frequency Prot.
0.00 .. 600.00 sec
Frequency Prot.
ON: Alarm only
ON: with Trip
OFF
Frequency Prot.
45.50 .. 54.50 Hz
Frequency Prot.
55.50 .. 64.50 Hz
Frequency Prot.
0.00 .. 600.00 sec
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
1.0 .. 170.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
1.0 .. 170.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
1.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
1.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
ON
OFF
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
OFF
ON
Voltage Prot.
OFF
ON
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U>Alarm U>>Trip
Voltage Prot.
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
2.0 .. 220.0 V; ∞
Voltage Prot.
0.00 .. 100.00 sec; ∞
Setting Options
Default Setting
ON: Alarm only
47.50 Hz
59.50 Hz
3.00 sec
ON: Alarm only
51.00 Hz
62.00 Hz
30.00 sec
OFF
85.0 V
2.00 sec
100.0 V
1.00 sec
0.98
OFF
150.0 V
2.00 sec
175.0 V
1.00 sec
0.98
OFF
30.0 V
2.00 sec
50.0 V
1.00 sec
ON
0.95
OFF
150.0 V
2.00 sec
175.0 V
1.00 sec
OFF
OFF
0.98
OFF
30.0 V
2.00 sec
50.0 V
1.00 sec
C53000-G1176-C145-6, Release date 02.2011
Comments
Over/Under Frequency Protec-
tion stage f3
f3 Pickup
f3 Pickup
T f3 Time Delay
Over/Under Frequency Protec-
tion stage f4
f4 Pickup
f4 Pickup
T f4 Time Delay
Operating mode Uph-e overvolt-
age prot.
Uph-e> Pickup
T Uph-e> Time Delay
Uph-e>> Pickup
T Uph-e>> Time Delay
Uph-e>(>) Reset ratio
Operating mode Uph-ph over-
voltage prot.
Uph-ph> Pickup
T Uph-ph> Time Delay
Uph-ph>> Pickup
T Uph-ph>> Time Delay
Uph-ph>(>) Reset ratio
Operating mode 3U0 (or Ux) ov-
ervoltage
3U0> Pickup (or Ux>)
T 3U0> Time Delay (or T Ux>)
3U0>> Pickup (or Ux>>)
T 3U0>> Time Delay (or T Ux>>)
3U0>(>): Stabilization 3U0-Mea-
surement
3U0>(>) Reset ratio (or Ux)
Operating mode U1 overvoltage
prot.
U1> Pickup
T U1> Time Delay
U1>> Pickup
T U1>> Time Delay
U1> with Compounding
U1>> with Compounding
U1>(>) Reset ratio
Operating mode U2 overvoltage
prot.
U2> Pickup
T U2> Time Delay
U2>> Pickup
T U2>> Time Delay
SIPROTEC, 7SD610, Manual