Settings - Siemens SIPROTEC 7SD610 Manual

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

The delay time T-PoleDiscrep. (address 3932) indicates how long a circuit breaker pole discrepancy con-
dition of the feeder circuit breaker, i.e. only one or two poles open, may be present before the pole discrepancy
supervision issues a 3-pole trip command. This time must be clearly longer than the duration of a 1-pole auto-
matic reclose cycle. The time should be less than the permissible duration of an unbalanced load condition
which is caused by the unsymmetrical position of the circuit breaker poles. Conventional values are 2 s to 5 s.
2.13.3

Settings

The table indicates region-specific presettings. Column C (configuration) indicates the corresponding second-
ary nominal current of the current transformer.
Addr.
Parameter
3901
FCT BreakerFail
3902
I> BF
3903
1p-RETRIP (T1)
3904
T1-1pole
3905
T1-3pole
3906
T2
3907
T3-BkrDefective
3908
Trip BkrDefect.
3909
Chk BRK CONTACT
3912
3I0> BF
3913
T2StartCriteria
3921
End Flt. stage
3922
T-EndFault
3931
PoleDiscrepancy
3932
T-PoleDiscrep.
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
C
Setting Options
ON
OFF
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
NO
YES
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec; ∞
NO
with T1-trip
with T2-trip
w/ T1/T2-trip
NO
YES
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
With exp. of T1
Parallel withT1
ON
OFF
0.00 .. 30.00 sec; ∞
ON
OFF
0.00 .. 30.00 sec; ∞
2.13 Circuit Breaker Failure Protection
Default Setting
ON
Breaker Failure Protection
0.10 A
Pick-up threshold I>
0.50 A
YES
1pole retrip with stage T1
(local trip)
0.00 sec
T1, Delay after 1pole start
(local trip)
0.00 sec
T1, Delay after 3pole start
(local trip)
0.15 sec
T2, Delay of 2nd stage
(busbar trip)
0.00 sec
T3, Delay for start with de-
fective bkr.
NO
Trip output selection with
defective bkr
YES
Check Breaker contacts
0.10 A
Pick-up threshold 3I0>
0.50 A
Parallel withT1
T2 Start Criteria
OFF
End fault protection
2.00 sec
Trip delay of end fault pro-
tection
OFF
Pole Discrepancy supervi-
sion
2.00 sec
Trip delay with pole dis-
crepancy
Functions
Comments
193