Functions
2.2 Protection Data Interfaces and Protection Data Topology
Addr.
Parameter
4509
T-DATA DISTURB
4510
T-DATAFAIL
4511
PI1 SYNCMODE
4512
Td ResetRemote
4513A
PROT1 max ERROR
4515A
PI1 BLOCK UNSYM
4801
GPS-SYNC.
4803A
TD GPS FAILD

2.2.3.3 Information List

No.
Information
3215
Wrong Firmware
3217
PI1 Data reflec
3227
>PI1 light off
3229
PI1 Data fault
3230
PI1 Datafailure
3233
DT inconsistent
3234
DT unequal
3235
Par. different
3239
PI1 TD alarm
3243
PI1 with
3245
>GPS failure
3247
GPS loss
3248
PI 1 GPS sync.
3250
PI 1 PD unsym.
3252
>SYNC PI1 RESET
3254
PI1 jump
3256
PI1 unsym.
3258
PI1 Error
3274
PI1: C37.94 n/a
62
Setting Options
0.05 .. 2.00 sec
0.0 .. 60.0 sec
TEL and GPS
TEL or GPS
GPS SYNC OFF
0.00 .. 300.00 sec; ∞
0.5 .. 20.0 %
YES
NO
ON
OFF
0.5 .. 60.0 sec
Type of In-
formation
OUT
Incompatible Firmware Versions
OUT
Prot Int 1: Own Datas received
SP
>Prot Int 1: Transmitter is switched off
OUT
Prot Int 1: Reception of faulty data
OUT
Prot Int 1: Total receiption failure
OUT
Device table has inconsistent numbers
OUT
Device tables are unequal
OUT
Differences between common parameters
OUT
Prot Int 1: Transmission delay too high
VI
Prot Int 1: Connected with relay ID
SP
> GPS failure from external
OUT
GPS: local pulse loss
OUT
GPS: Prot Int 1 is GPS sychronized
OUT
GPS:PI1 unsym.propagation delay too high
SP
> PI1 Synchronization RESET
OUT
Prot.1: Delay time change recognized
IntSP
Prot.1: Delay time unsymmetry to large
OUT
ProtInt1:Permissible error rate exceeded
OUT
PI1: IEEE C37.94 not supported by module
Default Setting
0.10 sec
Time delay for data disturbance
alarm
6.0 sec
Time del for transmission failure
alarm
TEL and GPS
PI1 Synchronizationmode
0.00 sec
Remote signal RESET DELAY for
comm.fail
1.0 %
Prot 1: Maximal permissible error
rate
YES
Prot.1: Block. due to unsym. delay
time
OFF
GPS synchronization
2.1 sec
Delay time for local GPS-pulse
loss
Comments