Default Settings; Leds; Binary Input; Binary Output - Siemens SIPROTEC 7SD610 Manual

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

Appendix

A.4 Default Settings

A.4

Default Settings

A.4.1

LEDs

Table A-1
LEDs
LED1
LED2
LED3
LED4
LED5
LED6
LED7
A.4.2

Binary Input

Table A-2
Binary Input
BI1
BI2
BI3
BI4
BI5
BI7
A.4.3

Binary Output

Table A-3
Binary Output
BO1
BO2
BO3
BO4
BO5
382
LED Indication Presettings
Allocated Func-
Function No.
tion
Relay TRIP
511
Relay PICKUP L1
503
Relay PICKUP L2
504
Relay PICKUP L3
505
Par. different
3235
PI1 Data fault
3229
DT inconsistent
3233
DT unequal
3234
Equal IDs
3487
Binary input presettings for all devices and ordering variants
Allocated Func-
Function No.
tion
>Intertrip 3pol
3504
>Reset LED
5
> Diff block
3525
>DTT Trip L123
4417
>BLOCK O/C I>>
7104
>BLOCK O/C I>
7105
>BLOCK O/C Ip
7106
>BLOCK O/C Ie>>
7107
>BLOCK O/C Ie>
7108
>BLOCK O/C Iep
7109
>BLOCK I-STUB
7130
>BLOCK O/CIe>>> 7132
>BLOCK Dir. I>
7111
>BLOCK Dir. Ip
7112
>CB1 Ready
371
Output relay presettings for all devices and ordering variants
Allocated Func-
Function No.
tion
Relay PICKUP L1
503
Relay PICKUP L2
504
Relay PICKUP L3
505
Relay TRIP
511
Relay TRIP
511
Description
Relay GENERAL TRIP command
Relay PICKUP Phase L1
Relay PICKUP Phase L2
Relay PICKUP Phase L3
Differences between common parameters
Prot Int 1: Reception of faulty data
Device table has inconsistent numbers
Device tables are unequal
Equal IDs in constellation
Description
I.Trip: >Intertrip 3 pole signal input
>Reset LED
>Differential protection blocking signal
>Direct Transfer Trip INPUT 3ph L123
>BLOCK Backup OverCurrent I>>
>BLOCK Backup OverCurrent I>
>BLOCK Backup OverCurrent Ip
>BLOCK Backup OverCurrent Ie>>
>BLOCK Backup OverCurrent Ie>
>BLOCK Backup OverCurrent Iep
>BLOCK I-STUB
>BLOCK Backup OverCurrent Ie>>>
>BLOCK direct. Backup OverCurrent I>
>BLOCK direct. Backup OverCurrent Ip
>CB1 READY (for AR,CB-Test)
Description
Relay PICKUP Phase L1
Relay PICKUP Phase L2
Relay PICKUP Phase L3
Relay GENERAL TRIP command
Relay GENERAL TRIP command
C53000-G1176-C145-6, Release date 02.2011
SIPROTEC, 7SD610, Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents