Siemens SIPROTEC 7SD610 Manual page 395

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

Addr.
Parameter
3749A
U2>(>) RESET
3751
Uph-e<(<)
3752
Uph-e<
3753
T Uph-e<
3754
Uph-e<<
3755
T Uph-e<<
3758
CURR.SUP. Uphe<
3759A
Uph-e<(<) RESET
3761
Uph-ph<(<)
3762
Uph-ph<
3763
T Uph-ph<
3764
Uph-ph<<
3765
T Uphph<<
3768
CURR.SUP.Uphph<
3769A
Uphph<(<) RESET
3771
U1<(<)
3772
U1<
3773
T U1<
3774
U1<<
3775
T U1<<
3778
CURR.SUP.U1<
3779A
U1<(<) RESET
3901
FCT BreakerFail
3902
I> BF
3903
1p-RETRIP (T1)
3904
T1-1pole
3905
T1-3pole
3906
T2
3907
T3-BkrDefective
3908
Trip BkrDefect.
3909
Chk BRK CONTACT
3912
3I0> BF
3913
T2StartCriteria
3921
End Flt. stage
3922
T-EndFault
3931
PoleDiscrepancy
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
Function
C
Voltage Prot.
0.30 .. 0.99
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
Voltage Prot.
1.0 .. 100.0 V; 0
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
1.0 .. 100.0 V; 0
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
ON
OFF
Voltage Prot.
1.01 .. 1.20
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
Voltage Prot.
1.0 .. 175.0 V; 0
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
1.0 .. 175.0 V; 0
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
ON
OFF
Voltage Prot.
1.01 .. 1.20
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
Voltage Prot.
1.0 .. 100.0 V; 0
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
1.0 .. 100.0 V; 0
Voltage Prot.
0.00 .. 100.00 sec; ∞
Voltage Prot.
ON
OFF
Voltage Prot.
1.01 .. 1.20
Breaker Failure
ON
OFF
Breaker Failure
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
Breaker Failure
NO
YES
Breaker Failure
0.00 .. 30.00 sec; ∞
Breaker Failure
0.00 .. 30.00 sec; ∞
Breaker Failure
0.00 .. 30.00 sec; ∞
Breaker Failure
0.00 .. 30.00 sec; ∞
Breaker Failure
NO
with T1-trip
with T2-trip
w/ T1/T2-trip
Breaker Failure
NO
YES
Breaker Failure
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
Breaker Failure
With exp. of T1
Parallel withT1
Breaker Failure
ON
OFF
Breaker Failure
0.00 .. 30.00 sec; ∞
Breaker Failure
ON
OFF
Setting Options
Default Setting
0.98
OFF
30.0 V
2.00 sec
10.0 V
1.00 sec
ON
1.05
OFF
50.0 V
2.00 sec
17.0 V
1.00 sec
ON
1.05
OFF
30.0 V
2.00 sec
10.0 V
1.00 sec
ON
1.05
ON
0.10 A
0.50 A
YES
0.00 sec
0.00 sec
0.15 sec
0.00 sec
NO
YES
0.10 A
0.50 A
Parallel withT1
OFF
2.00 sec
OFF
Appendix
A.7 Settings
Comments
U2>(>) Reset ratio
Operating mode Uph-e under-
voltage prot.
Uph-e< Pickup
T Uph-e< Time Delay
Uph-e<< Pickup
T Uph-e<< Time Delay
Current supervision (Uph-e)
Uph-e<(<) Reset ratio
Operating mode Uph-ph under-
voltage prot.
Uph-ph< Pickup
T Uph-ph< Time Delay
Uph-ph<< Pickup
T Uph-ph<< Time Delay
Current supervision (Uph-ph)
Uph-ph<(<) Reset ratio
Operating mode U1 undervolt-
age prot.
U1< Pickup
T U1< Time Delay
U1<< Pickup
T U1<< Time Delay
Current supervision (U1)
U1<(<) Reset ratio
Breaker Failure Protection
Pick-up threshold I>
1pole retrip with stage T1 (local
trip)
T1, Delay after 1pole start (local
trip)
T1, Delay after 3pole start (local
trip)
T2, Delay of 2nd stage (busbar
trip)
T3, Delay for start with defective
bkr.
Trip output selection with defec-
tive bkr
Check Breaker contacts
Pick-up threshold 3I0>
T2 Start Criteria
End fault protection
Trip delay of end fault protection
Pole Discrepancy supervision
395