2.1.3.2 Setting Notes

General
If multiple setting groups are not required. Group A is the default selection. Then, the rest of this section is not
applicable.
If multiple setting groups are desired, the setting group change option must be set to Grp Chge OPTION =
Enabled in the relay configuration of the functional scope (Section 2.1.1.2, address 103). Now the 4 setting
groups A to D are available. They are configured individually as required in the following. To find out how to
proceed, how to copy and to reset settings groups to the delivery state, and how to switch between setting
groups during operation, please refer to the SIPROTEC 4 System Description.
Two binary inputs enable changing between the 4 setting groups from an external source.

2.1.3.3 Settings

Addr.
Parameter
301
ACTIVE GROUP
302
CHANGE

2.1.3.4 Information List

No.
Information
-
P-GrpA act
-
P-GrpB act
-
P-GrpC act
-
P-GrpD act
7
>Set Group Bit0
8
>Set Group Bit1
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
Setting Options
Group A
Group B
Group C
Group D
Group A
Group B
Group C
Group D
Binary Input
Protocol
Type of In-
formation
IntSP
Setting Group A is active
IntSP
Setting Group B is active
IntSP
Setting Group C is active
IntSP
Setting Group D is active
SP
>Setting Group Select Bit 0
SP
>Setting Group Select Bit 1
Default Setting
Group A
Active Setting Group is
Group A
Change to Another Setting Group
Comments