Fault Reactions - Siemens SIPROTEC 7SD610 Manual

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

Functions
2.15 Monitoring Functions
Figure 2-94

2.15.1.5 Fault Reactions

Depending on the kind of fault detected, an alarm is given, the processor is restarted or the device is taken out
of operation. After three unsuccessful restart attempts, the device is taken out of service. The device ready
relay drops out and indicates the device failure with its NC contact („life contact"). The red LED „ERROR" on
the device front lights up, provided that there is an internal auxiliary voltage, and the green LED „RUN" goes
off. If the internal auxiliary voltage supply fails, all LEDs are dark. Table 2-7 shows a summary of the monitoring
functions and the malfunction responses of the device.
212
Logic of the Positive Sequence System Phase Angle Monitoring
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011