Pickup Logic Of The Entire Device - Siemens SIPROTEC 7SD610 Manual

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

Functions
2.16 Function Control and Circuit Breaker Test
1-pole Dead Time
During a 1-pole dead time, the load current flowing in the two healthy phases forces a current flow via earth
which may cause undesired pickup. The raising zero-sequence voltage can also produce undesired responses
of the functions.
The indications „1pole open L1" (No. 591), „1pole open L2" (No. 592) and „1pole open L3" (No.
593) are additionally generated if the „Open Pole Detector" detects that current and voltage are absent in one
phase – while current flow is detected in both other phases. In this case, one of the indications will only be main-
tained while the condition is met. This enables a single-pole automatic reclosure to be detected on an unloaded
line.
Specially for applications with busbar side voltage transformers the indication „1pole open Lx" is addition-
ally transmitted if the phase-selective CB auxiliary contacts clearly show a single-pole open circuit breaker, and
the current of the affected phase falls below the parameter 1130 PoleOpenCurrent.
Depending on the setting of parameter 1136 OpenPoleDetect., the Open Pole Detector evaluates all avail-
able measured values including the auxiliary contacts (default setting w/ measurement) or it processes only
the information from the auxiliary contacts including the phase current values (setting Current AND CB). To
disable the Open Pole Detector, set parameter 1136 to OFF.

2.16.1.4 Pickup Logic of the Entire Device

Phase Segregated Fault Detection
The fault detection logic combines the fault detection (pickup) signals of all protection functions. In the case of
those protection functions that allow for phase segregated pickup, the pickup is output in a phase segregated
manner. If a protection function detects an earth fault, this is also output as a common device alarm. Thus, the
alarms „Relay PICKUP L1", „Relay PICKUP L2", „Relay PICKUP L3" and „Relay PICKUP E" are
available.
The above alarms can be allocated to LEDs or output relays. For the local display of fault event messages and
for the transmission of event messages to a personal computer or a centralized control system, several protec-
tion functions provide the possibility to display the faulted phase information in a single message, e.g. „Diff
Flt. L12E" for a differential protection pickup L1-L2-E.
General Pickup
The pickup signals are combined with OR and lead to a general pickup of the device. It is signalled with „Relay
PICKUP". If no function of the device is picked up any longer, „Relay PICKUP" disappears (indication
„OFF").
General device pickup is a precondition for a series of internal and external functions that occur subsequently.
The following are among the internal functions controlled by general device pickup:
• Opening of a trip log: from general device pickup to general device dropout, all fault indications are entered
in the trip log.
• Initialization of fault record: the storage and maintenance of fault values can also be made dependent on the
occurrence of a trip command.
• Generation of spontaneous indications: Certain fault indications can be displayed as spontaneous indica-
tions (see margin heading „Spontaneous Indications"). In addition, this indication can be made dependent
on the general device trip.
• Start action time of automatic reclosure (if available and used).
External functions may be controlled by this indication via an output contact. Examples are:
• Automatic reclose devices,
• Further additional devices or similar.
230
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents