7SG13 Delta P20064 FM1 Autoreclosing Section 1: Introduction 1.1 Introduction This document covers the auto-reclose function and its features. A Diagrams and Parameters document which covers each individual model is available, which lists explicitly the functions that are provided and the manner in which they are connected.
7SG13 Delta P20064 FM1 Autoreclosing Section 2: Element Definitions 2.1 Auto-reclose control Delayed Auto-Reclose (DAR) is initiated by a valid trip relay operation while the associated circuit breaker is in service. A circuit breaker’s service status is determined by its position. The circuit breaker is defined as being in service when it is closed.
7SG13 Delta P20064 FM1 Autoreclosing 2.1.5 In/Out Switching The DAR feature may be switched out by changing the A/R In Service setting by a number of methods. These are either a keypad change from the front panel, or via a communication, or by an A/R OUT status input. A/R OUT status input has priority over A/R IN.
7SG13 Delta P20064 FM1 Autoreclosing 2.1.12 Metering The Status of the DAR operations are displayed in Meters under the instruments Menu. 2.1.13 Dead-time and Reclaim Timing The Deadtime will start if a Trip has occurred and the CB is Open and the Trip and Starter have then reset and the line has gone dead.
Page 7
7SG13 Delta P20064 FM1 Autoreclosing Setting name Range (bold = default) Units Notes Sub-menu: Output Relays Lockout A/R Switched Out A/R In Progress Successful Close _, 1 for each output contact Line Check Ext Arc Start CBFailedToOpen CBFailedToClose Sub-menu: Status Inputs...