Functions
2.9 Backup Time Overcurrent Protection
Accordingly, the earth current stage 3I0> STUB (address 2632) should pick up on the smallest earth current
to be expected during an earth fault and the delay T 3I0 STUB (address 2633) should exceed the base time
of the differential protection by one grading time. If only the phase currents are to be monitored, set the pickup
value of the earth current stage to ∞.
The I>>> stage can also be accelerated by the release signal „>O/C InstTRIP" (no. 7110) e.g. before au-
tomatic reclosing. This is defined using parameter I-STUB Telep/BI (address 2634). Set this parameter to
YES if you want the I>>> stage to trip instantaneously while the binary input „>O/C InstTRIP" is active or
the internal automatic reclosing function is ready to operate.
Instantaneous tripping by the operational auto-reclosure should only be chosen if the I>>> stage is set as an
emergency function. If the differential protection is out of operation, this emergency stage guarantees instan-
taneous tripping before auto-reclosure.
Instantaneous tripping when the line is switched onto a fault is also possible with the I>>> stage. Set parameter
I-STUB SOTF (address 2635) to YES if instantaneous tripping is desired.
2.9.4

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding second-
ary nominal current of the current transformer.
Addr.
Parameter
2601
Operating Mode
2602
SOTF Time DELAY
2603A
Direct. 3I0
2610
Iph>>
2611
T Iph>>
2612
3I0>> PICKUP
2613
T 3I0>>
2614
I>> Telep/BI
2615
I>> SOTF
2620
Iph>
2621
T Iph>
2622
3I0>
2623
T 3I0>
120
C
Setting Options
ON
Only Emer. prot
OFF
0.00 .. 30.00 sec
U0/I0 or U2/I0
with U0/I0
with U2/I2
1A
0.05 .. 50.00 A; ∞
5A
0.25 .. 250.00 A; ∞
0.00 .. 30.00 sec; ∞
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞
0.00 .. 30.00 sec; ∞
NO
YES
NO
YES
1A
0.05 .. 50.00 A; ∞
5A
0.25 .. 250.00 A; ∞
0.00 .. 30.00 sec; ∞
1A
0.05 .. 25.00 A; ∞
5A
0.25 .. 125.00 A; ∞
0.00 .. 30.00 sec; ∞
Default Setting
ON
Operating mode
0.00 sec
Trip time delay after SOTF
U0/I0 or U2/I0
Measurement of direction
for 3I0
2.00 A
Iph>> Pickup
10.00 A
0.30 sec
T Iph>> Time delay
0.50 A
3I0>> Pickup
2.50 A
2.00 sec
T 3I0>> Time delay
YES
Instantaneous trip via Tele-
prot./BI
NO
Instantaneous trip after
SwitchOnToFault
1.50 A
Iph> Pickup
7.50 A
0.50 sec
T Iph> Time delay
0.20 A
3I0> Pickup
1.00 A
2.00 sec
T 3I0> Time delay
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011