Information List - Siemens SIPROTEC 7SD610 Manual

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

Functions
2.1 General
Addr.
Parameter
1130A
PoleOpenCurrent
1131A
PoleOpenVoltage
1132A
SI Time all Cl.
1133A
T DELAY SOTF
1134
Line Closure
1135
Reset Trip CMD
1136
OpenPoleDetect.
1150A
SI Time Man.Cl
1151
SYN.MAN.CL
1152
Man.Clos. Imp.
1155
3pole coupling
1156A
Trip2phFlt
1161
VECTOR GROUP U
1162
VECTOR GROUP I
1163
TRANS STP IS

2.1.4.3 Information List

No.
Information
301
Pow.Sys.Flt.
302
Fault Event
351
>CB Aux. L1
352
>CB Aux. L2
353
>CB Aux. L3
356
>Manual Close
48
C
Setting Options
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
2 .. 70 V
0.01 .. 30.00 sec
0.05 .. 30.00 sec
only with ManCl
I OR U or ManCl
CB OR I or M/C
I or Man.Close
CurrentOpenPole
Current AND CB
Pickup Reset
OFF
Current AND CB
w/ measurement
0.01 .. 30.00 sec
w/o Sync-check
NO
(Setting options depend
on configuration)
with PICKUP
with TRIP
3pole
1pole leading Ø
1pole lagging Ø
0 .. 11
0 .. 11
Solid Earthed
Not Earthed
Type of In-
formation
OUT
Power System fault
OUT
Fault Event
SP
>Circuit breaker aux. contact: Pole L1
SP
>Circuit breaker aux. contact: Pole L2
SP
>Circuit breaker aux. contact: Pole L3
SP
>Manual close signal
Default Setting
0.10 A
Pole Open Current
Threshold
0.50 A
30 V
Pole Open Voltage
Threshold
0.10 sec
Seal-in Time after ALL clo-
sures
0.25 sec
minimal time for line open
before SOTF
I or Man.Close
Recognition of Line Clo-
sures with
CurrentOpenPole
RESET of Trip Command
w/ measurement
open pole detector
0.30 sec
Seal-in Time after
MANUAL closures
NO
Manual CLOSE
COMMAND generation
None
MANUAL Closure Impulse
after CONTROL
with TRIP
3 pole coupling
3pole
Trip type with 2phase
faults
0
Vector group numeral for
voltage
0
Vector group numeral for
current
Solid Earthed
Transformer starpoint is
Comments
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
Comments

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents