General Power System Data (Power System Data 1); Setting Notes - Siemens SIPROTEC 7SD610 Manual

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

Functions
2.1 General
2.1.2

General Power System Data (Power System Data 1)

The device requires some plant and power system data in order to be able to adapt its functions accordingly,
depending on the actual application. The data required include for instance rated data of the substation and the
measuring transformers, polarity and connection of the measured quantities, if necessary features of the circuit
breakers, and others. Furthermore, there are several function parameters associated with several functions
rather than one specific protection, control or monitoring function. The Power System Data 1 can only be
changed from a PC running DIGSI and are discussed in this section.

2.1.2.1 Setting Notes

Current Transformer Polarity
In address 201 CT Starpoint, the polarity of the current transformers must be entered, in other words, the
location of the CT star-point (Figure 2-1). The setting defines the measuring direction of the device (current in
line direction is defined as positive at both line ends). The reversal of this parameter also reverses the polarity
of the earth current input I
Figure 2-1
Nominal Values of Transformers
In principle, the differential protection does not require any measured voltage. However, voltages can be con-
nected. These voltages allow to display and log voltages, and to calculate various components of power. If nec-
essary, they can also serve for determining the life line condition in case of automatic reclosure. During config-
uration of the device functions (Subsection 2.1.1), it has been determined whether the device is to work with or
without measured voltages.
In addresses 203 Unom PRIMARY and 204 Unom SECONDARY the device obtains information on the primary
and secondary rated voltage (phase-to-phase voltage) of the voltage transformers; in address 205 CT
PRIMARY and 206 CT SECONDARY the primary and secondary rated current transformers are set.
It is important to ensure that the secondary CT nominal current matches the rated current of the device, other-
wise the device will be blocked. The nominal current is set with jumpers on the measuring module (see 3.1.2).
Correct entry of the primary data is a prerequisite for the correct computation of operational measured values
with primary magnitude. If the settings of the device are performed with primary values using DIGSI, these
primary data are an indispensable requirement for the correct function of the device.
34
.
E
Polarity of current transformers
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents