2.17.5
Differential Protection Values
2.17.5.1 Measured values of differential protection
The differential and restraint current values of the differential protection which are listed in the following table
can be called up at the front of the device, read out via the operating interface using a PC with DIGSI or trans-
ferred to a control centre via the system interface.
Table 2-12
Measured values of the differential protection
IDiff
, IDiff
, IDiff
L1
L2
L3
IRest
, IRest
, IRest
L1
L2
L3
IDiff
3I0
1)
for lines according to address (see section 2.1.4), for transformers calculated from address (see Section 2.1.4)
I
= S
/(√3 · U
)
N
N
N

2.17.5.2 Information List

No.
Information
7742
IDiffL1=
7743
IDiffL2=
7744
IDiffL3=
7745
IRestL1=
7746
IRestL2=
7747
IRestL3=
7748
Diff3I0=
30654
IdiffREF=
30655
IrestREF=
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
Measured Values
Calculated differential currents of the three phases
Calculated restraining currents of the three phases
Calculated differential current of the zero sequence system
Type of In-
formation
MV
MV
MV
MV
MV
MV
MV
MV
MV
Comments
IDiffL1(% Operational nominal current)
IDiffL2(% Operational nominal current)
IDiffL3(% Operational nominal current)
IRestL1(% Operational nominal current)
IRestL2(% Operational nominal current)
IRestL3(% Operational nominal current)
Diff3I0 (Differential current 3I0)
Idiff REF(% Operational nominal current)
Irest REF(% Operational nominal current)
Functions
2.17 Additional Functions
% Referred to
Nominal operational current
Nominal operational current
Nominal operational current
1)
1)
1)
253