Siemens SIPROTEC 7SD610 Manual page 328

Hide thumbs Also See for SIPROTEC 7SD610:
Table of Contents

Advertisement

Technical Data
4.1 General
Profibus DP Fibre Optical Link
DNP3.0 / MODBUS RS485
DNP3.0 / MODBUS FO
Ethernet electrical (EN 100) for
IEC 61850 and DIGSI
328
FOC connector type
Connection for flush mounting housing
Connection for surface mounting housing please use version with Profibus RS485 in the
Transmission rate
Recommended speed:
Optical Wavelength
Laser Class I according to EN 60825-1/-2 using glass fibre 50 μm/125 μm oder
Permissible path attenuation
Transmission distance between two
modules with redundant optical ring topol-
ogy and optical fibre 62.5/125 m
Character idle state (status for "No charac-
ter")
Max. number of modules in optical rings
with 500 kB/s or 1500 kB/s
Connection for flush mounting housing
Connection for surface mounting housing in console housing
Test voltage
Transmission rate
Bridgeable distance
FOC connector type
Connection for flush mounting housing
Connection for surface mounting housing in console housing
Transmission rate
Optical Wavelength
Laser class 1 according EN 60825-1/-2
Permissible path attenuation
Bridgeable distance
Connection for flush-mounted housing
Connection for surface mounting housing In console housing on bottom
Test voltage (female connector)
Transmission rate
Bridgeable distance
ST connector; double ring
Rear panel, mounting location „B"
console housing as well as separate electri-
cal/optical converter.
Conversion by means of external OLM up to
1.5 MBaud
≥ 500 kBaud for normal version
≤ 57600 Baud with detached operator panel
> 500 kBaud
λ = 820 nm
using glass fibre 62,5 μm/125 μm
max. 8 dB, with glass fibre 62,5 μm/125 μm
2 m (6.6 ft.) with plastic fibre
500 Kbits/s max. 1.6 km (5,250 ft.)
1500 Kbits/s 530 m (1,760 ft.)
Light OFF
41
Rear panel, slot „B",
9-pole D-subminiature female connector
500 V; 50 Hz
Up to 19200 Baud
Max. 1 km
ST connector receiver/transmitter
Rear panel, mounting location „B"
Up to 19200 Baud
λ = 820 nm
using glass fibre 50 μm/125 µm oder
using glass fibre 62,5 μm/125 µm
max. 8 dB, with glass fibre 62,5 μm/125 µm
Max. 1.5 km
Rear panel, mounting location „B"
2 x RJ45 female connector
100BaseT according to IEEE802.3
500 V; 50 Hz
100 Mbits/s
20 m
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011

Hide quick links:

Advertisement

Table of Contents
loading