16. Appendix G
16.1. Loading CIOM-A FIM firmware
Step
5
In the Look in field, click the
button to navigate to this directory
location c:\Program
Files\Honeywell\Experion\Enginee
ring Tools\system\firmware\FIM, if
required.
Open appropriate release version
folder and click fimboot.nvs file so it
appears in the File name field. Click
the Open button.
6
Click the Yes button to acknowledge that
you want to proceed with the update.
(Note that RDY should appear in the FIM
display)
7
Wait for the load to complete and the
CIOM-A FIM to reboot to its RDY state.
8
Click the OK button to acknowledge that
the update completed with no errors.
9
Check that the updated boot version (BV)
now appears on the CIOM-A FIM graphic
in green.
528
Experion PKS Series A Fieldbus Interface Module User's Guide
Action
Honeywell
Result
Opens Please Confirm Changes
message box. This illustration is for
example purposes only.
Initiates firmware load. LOAD
appears in the CIOM-A FIM display.
Progress of the load is tracked in
the status bar.
NetworkTools message box appears.
Wait for the Ntools to complete its next
scan.
R400
July 2010