Honeywell Series A User Manual page 237

Fieldbus interface module
Hide thumbs Also See for Series A:
Table of Contents

Advertisement

Scenario
of a CEE containing
a FF function block
to "Idle" or "Run.".
Deleting a Device,
Link, FIM or CM
containing an FF
function block
Enabling the
reporting of the Block
Offnet Diagnostic
Alarm for an
individual FF function
block when the
device is online.
(The precondition is
that the Block Offnet
Diagnostic Alarm is
configured not to be
reported for the
function block, when
the device goes off
the network.)
Enabling the
reporting of the Block
Offnet Diagnostic
Alarm for an
individual FF function
block when the
device is off the
network.
(The precondition is
that the Block Offnet
Diagnostic Alarm is
configured not to be
reported for the
function block, when
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
Behavior of Block Offnet Alarm
containing Control Modules,
which contain Fieldbus blocks,
has no effect on the alarms
reported by the Fieldbus blocks.
No alarms are reported for device
offnet conditions.
A change event is logged in the
Event Summary indicating
OFFNETALM_ENABLED is set to
ON.
A high-priority Block Offnet Alarm
is reported for that function block.
A change event is logged in the
Event Summary indicating
OFFNETALM_ENABLED is set to
ON.
Honeywell
5. Configuration
5.7. Block Offnet Diagnostic Alarm
Behavior of Device Offnet System
Alarm
containing Control Modules, which
in turn contain Fieldbus blocks, has
no effect on the alarms reported by
the Fieldbus blocks.
No alarms are reported for device
offnet conditions.
A high-priority Device Offnet
System Alarm is reported for the
device, when the device goes
offnet. There is no change in the
system alarm.
237