Checking Device - Honeywell Series A User Manual

Fieldbus interface module
Hide thumbs Also See for Series A:
Table of Contents

Advertisement

7. Fieldbus Device Commissioning

7.3. Checking Device

Stage
Return to Stage 9
18
Is lowest signal level over 150 millivolts?
NO > Go to Stage 19
YES > Go to Stage 20
19
Insufficient power for device. Check power supply and link
design.
Return to Stage 9
20
Is there an addressing issue?
NO > Go to Stage 21
YES > Go to Stage 22
21
Device should be present. Replace the device.
Return to Stage 9
22
Check if address is in unpolled range, check for too many
devices with temporary address.
References:
Tags, Addresses, and Live List
Return to Stage 9
7.3
Checking Device
Stage
23
Does firmware - DD Revision match device revision?
NO > Go to Stage 24
Yes > Go to Stage 25
24
Upgrade firmware or import new DD file
References:
Replacing Device Template with a Different One
282
Experion PKS Series A Fieldbus Interface Module User's Guide
Funtion
Funtion
Honeywell
Completed
Completed
R400
July 2010

Advertisement

Table of Contents
loading

This manual is also suitable for:

Experion pks series a

Table of Contents